aquastar MT pH/ORP/T
/
/
aquastar MT pH/ORP/T
aquastar MT pH/ORP/T
Intelligent measurement electronics for pH, redox, and temperature sensors with a digital RS485 Modbus RTU interface and an analog 4–20 mA output via an M12 connector.

The aquastar MT pH/ORP/T is a measurement electronics unit that is mounted directly on a pH or redox sensor and transmits the measured values to a measurement or automation device, either digitally via RS485 Modbus RTU or analog as a 2-wiretransmitter with a scalable 4–20 mA signal. The electronics are available with an N-connection, BNC connector, or Variopin and are connected via a 5-pin M12 connector.

Typical applications include aquaculture and fish farming, marine research and aquariums, water and wastewater, food and beverages, chemicals, power plants, environmental monitoring, and other industrial liquid analysis. In digital operation, the cable between the sensor and the measuring equipment can be up to 1,000 m long.

Calibration data is stored in the electronics so that the sensor can be calibrated before commissioning, and the electronics can be reused when the sensor is replaced. The electronics detect glass breakage, cable breakage, and a dirty glass membrane; they feature a calibration timer, a calibration log with the last 10 calibrations, an hour meter, and temperature compensation via Pt1000.

Tekniske specifikationer

Sensortype

Andet

Måleområde, min.

-1

Måleområde, maks.

15

Måleenhed

pH

Nøjagtighed

< 1 mV ved pH 7

Outputsignal

4-20mA

Forsyningsspænding

4,8-30 V DC (digital), 11,5-30 V DC (4-20 mA)

Elektrisk tilslutning

M12-stik

IP-klasse

IP67

Omgivelsestemperatur

-10°C til +60°C

Mål

ca. 121 mm (Variopin) / ca. 134 mm (N), Ø19,8 mm

Grænseflader

RS485 Modbus RTU, 4-20 mA (2-leder)

Opbevaringstemperatur

-10°C til +85°C

Godkendelser

DIN EN 61326-1 (EMC)

Vigtigste features

  • pH measuring range: -1 to 15 pH
  • Redox measuring range: -500 to +1700 mV
  • Temperature input: -10 to +100°C, Pt1000 in 2-wire circuit, ±0.2 °C
  • Digital interface RS485 Modbus RTU, address 1 to 247, 9600-115200 baud
  • Analog 4-20 mA output as 2-wire transmitter, accuracy typ. ±0.04 mA at 25 °C
  • Cable length up to 1000 m in digital operation
  • 5-pole M12 plug connector, A-coded
  • Available with N-connection, BNC plug or Variopin
  • Sensor monitoring: glass breakage, cable breakage and dirty glass membrane
  • Calibration logbook with the last 10 calibrations and calibration timer
  • Power consumption digital operation: 50 mW / 10 mA at 5 V
  • Galvanic isolation: DC 80 V / AC 42 V
  • EMC according to DIN EN 61326-1, emission class B
  • Relative humidity < 92 % annual average, no condensation
  • Dimensions: approx. 121 mm (Variopin) / approx. 134 mm (N-connection), Ø19.8 mm, M12x1

Har du spørgsmål til dette produkt?

Turnkey Control Solutions